10
STEP 1
STEP 2
STEP 3
POWER SUPPLY CORD
The HPAC 2.0 is shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power
supply cord. The LCDI device meets the UL and US National Electric Code 440.65 requirements for power supply
cord connected air conditioners.
TEST YOUR POWER SUPPLY CORD PRIOR TO INSTALLATION
Plug power supply cord into a grounded three-prong electrical power outlet.
Press TEST (listen for the click; Reset button trips and pops out). This should cut
the power to the HPAC 2.0. If the plug does not trip and the unit stays on, please
contact technical support.
Press RESET (listen for the click; Reset button latches and remains in). The power
supply cord is ready for operation.
The LCDI device is not intended to be used as a switch. Do not
use the TEST and RESET buttons to turn the HPAC 2.0 on and
off. Once plugged in, HPAC 2.0 will operate normally without the
need to reset the LCDI device.
CAUTION
ELECTRICAL SHOCK HAZARD
If the LCDI device fails to trip when tested or if the power supply
cord is damaged, it must be replaced with a new power supply
cord obtained from Ephoca and must not be repaired.
WARNING