Using the ID icon in the iRMC S5 web interface
â–¶
Log in to the iRMC S5 web interface.
The icon that represents the ID indicator LED resides on the right of the
menu bar. Its color symbolizes its status:
blue
: the ID LED is on.
grey: the ID LED is off.
â–¶
Click the icon to switch the ID indicator LED on or off.
Using ServerView Operations Manager
â–¶
In ServerView Operations Manager Single System View and press the
Locate button in the title bar to switch off the ID indicator.
5.3.19 Performing a fan test
Notes on replacing a defective fan
After replacing a defective system fan or PSU containing a defective fan,
the fan error indicators will stay lit until the next fan test. By default, a fan
test is automatically started every 24 hours. The first automatic fan test
being performed after replacing a fan will turn off the fan error indicator
.
If you want to start the fan test manually, you can do so by following the
description below:
Executing the fan test via the iRMC S5 web interface
â–¶
Log into the iRMC S5 web interface.
The System menu is displayed on default.
â–¶
Open the Cooling page.
â–¶
Expand the Cooling Devices group.
â–¶
Click Start Fan Test.
For more information on iRMC settings, see the iRMC user guides.
Basic software procedures
114 Upgrade and Maintenance Manual RX4770 M6