GEK-7303 Low Voltage
Power
Circuit
Breakers
1·· 2
. . . . . .
.
..
..
.
. :
:;.:
:
·:
:··:
~--
.
. .
,,
, '
.·. : ·· ...
.. .
. . :
.-
: :
Fig.
4 (8014830)
Disassembly
of
arc
quenchers-standard
breaker
and AKF
center
pole
.
1. Stud
2. Cap
3. Side
Barrier
4.
Pocket
Barrie~
5.
Inner
Barrier
DISASSEMBL
Y~AK
AND
AKF
CENTER
POLE
(Fig.
4) -
The following
instructions
apply
to
both
tl1e
Type
AK
and AKF
breaker
center
poles.
1. Remove
arc
quenchers
(see
REPLACE-
MENT).
2. Remove
screws
holding
spacer
block (9).
3. Remove
spacer
block,
steel
back
plate
(8), and compound support (7).
4. Rock muffler
(6)
slightly and
remove.
The
inner
barriers
(5)
can now be
removed
for
inspection.
5. Remove nut and withdraw
stud
(1).
6. Remove cap (2). The
side
(3) and
pocket
(4)
barriers
should be
free.
7.
Reassemble and
replace
the
arc
quencher
in
the
reverse
order.
Tighten
the
fastenings
after
replacement.
DISASSEMBLY-
AKF
OUTER
POLES
(Fig.
5)
1.
Remove
arc
quenchers
(8Ce
abov
e)
and
lay
on
sides
on a flat surface. ··
2. Remove hardware
from
one
side
of
arc
quencher
as
indicated in Fig. 5.
6. Muffler
7. Compound
Support
8.
Steel
Back
Plate
9.
Spacer
Block
3.
Remove
bolt
fastening
cap
(4)
and
barrier
plate
assembly.
4.
Barrier
plates
may now
be
lifted
from
as-
sembly
for
inspection.
5.
In
reassembling,
make
sure
· components
are
positioned
so
that
holes
for
self-tapping
hard-
ware
are
in
line.
Do not
strip
threads
in
compound
by
overstressing
screws.
POLE UNIT A
SSEMB
LY
(Fig. 6)
NOTE:
The
text
and
part
identification
numbers
contained
in
this
section
apply
to
illustrations
covering
the
AK-50
breaker.
The
same
text
is
·
applicable
to
the
AK
-
75
and 100
breakers
by
referring
to
Fig.
7 and identifying
the
similar
parts.
These
similar
parts
may not, in
every
case,
be
identified
by the
same
number
.
Each
pole
unit
assembly
consists
of a
set
of
arcing
contacts,
a
set
of mai~
contacts,
the
actuating linkage and the mounting
base.
See
Fig.
8
and
9, pole unit
assemblies
mounted on
back
frame
assemblies.
The
stationary
arcing-contact
assembly
con- ,
sists
of a
set
of
parallel
contact
fingers
(2),
pin
(3), and
compression
sprin
gs (22), which
provide
continuous contact
pres
s
ure
for
the
fu
ll

Table of Contents

Other manuals for GE AK-1-15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AK-1-15 and is the answer not in the manual?

GE AK-1-15 Specifications

General IconGeneral
BrandGE
ModelAK-1-15
CategoryCircuit breakers
LanguageEnglish

Related product manuals