EasyManuals Logo
Home>Harman>Indoor Fireplace>P35I

Harman P35I User Manual

Harman P35I
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
14
Save These Instructions3-90-775R36_09/15
C. Venting Requirements & Restrictions
Acombustionblowerisusedtoextractthecombustiongases
from the rebox. This causes a negative pressure in the
reboxandapositivepressureintheventingsystem.The
longer the vent pipe and more elbows used in the system,
thegreatertheowresistance.
TherecommendedmaximumuelengthsfortheP35i
Insertareasfollows:
4" Flex Pipe:
Maximum30Ft.Vertical
3" Flex Pipe:
Maximum20Ft.Vertical
LongrunsofexorPLventpipeinstalleddirectlyvertical
fromtheuestubmayrequiremorefrequentcleaningdue
toyashfallingoffinsideandcollectingdirectlyabovethe
combustion blower outlet.
Any use of horizontal venting will require more frequent
cleaning.Itistheresponsibilityoftheinstallertomakesure
theentireuecongurationisaccessibleforcleaning.
4" stainless steel ex vent piping is only allowed for use
in masonry replaces and chimneys or factory builtwood
burningreplaceswithclassAmetalchimneys.Allpelletvent
pipe must be secured together either by means provided by
pipe manufacturer or by 3 screws at each joint.
There are two different flue pipe stubs available. The unit
comes standard with the largest pipe stub.
1. Part#1-00-574034isforusewith4”PLventstarterpipe
and4”stainlesssteelexpipe(Part#1-00-574034).
2. Part#1-00-674039isforusewith3”PLventstarterpipe
andalsoforusewith3”aluminumexductforoutsideair
connections.
Useonlythespeciedventingcomponents.Useofany
other components will void the product warranty and
may pose a hazard.
Do Not Install A Flue Damper In The Exhaust Venting
SystemOfThisAppliance.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
WARNING! RISK OF FIRE!
OnlyLISTEDtypeLorPLPelletventingcomponents
may be used.
NOOTHERtypeofventingmaterialsorcomponents
may be used.
Substitute or damaged vent components may impair
safe operation.
WARNING! RISK OF INJURY OR PROPERTY DAMAGE!
Improper installation, adjustment, alteration, service,
or maintenance can cause injury or property damage.
Read and Refer to your owner's manual.
For assistance or additional information, consult a
qualiedinstaller,serviceagencyoryourdealer.
INCANADA:Thisreplaceinsertmustbeinstalledwith
acontinuouschimneylinerofaminimum3"diameter
extendingfromtheinserttothetopofthechimney.The
chimneylinermustconformtotheClass3requirements
of CAN/ULC-S635, Standard for Lining Systems for
Existing Masonry or Factory Built Chimneys and Vents,
or CAN/ULC-S640, Standard for Lining Systems for
New Masonry Chimneys.

Table of Contents

Other manuals for Harman P35I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Harman P35I and is the answer not in the manual?

Harman P35I Specifications

General IconGeneral
BrandHarman
ModelP35I
CategoryIndoor Fireplace
LanguageEnglish

Related product manuals