EasyManuals Logo
Home>Higen>Servo Drives>FDA6000C Series

Higen FDA6000C Series User Manual

Higen FDA6000C Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
Chapter 3. Wiring and Signals
3-14
Monitor Output 1 MONIT1 3
Outputs within the range of –4 +4 [V] according to
values set to [Monitor1 Select (P2-10)], [Monitor1 ABS
(P2-11)], [Monitor1 Scale (P2-12)], [Monitor1 offset (P2-
13)].
[Monitor1 Select] - 0: current position, 1: position error,
2: speed, 3: torque
Monitor Output 2 MONIT2 2
Outputs within the range of –4 +4 [V] according to
values set to [Monitor2 Select (P2-14)], [Monitor2 ABS
(P2-15)], [Monitor2 Scale (P2-16)], and [Monitor2 offset
(P2-17)].
[Monitor2 Select]- 0: current position, 1: position error,
2: speed, 3: torque
+12[V] Output +12V 35
-12[V]Output -12V 37
Output ±12[V] used only when speed override
command is simply applied.
0[V] 1
8
26
33
34
GND
36
This is the power supply common Ground
Terminal for analog speed Override Command,
positive speed monitor output, and encoder output
terminals.
F Pulse PPFIN 11
PFIN 10
PPRIN 9
R Pulse
PRIN 12
Set pulse forms according to the set value of the
parameter [Pulse Logic(P4-4)]Pulse form
Direction + Pulse
CW Pulse + CCW Pulse
Two phase pulse(Phase A + Phase B)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Higen FDA6000C Series and is the answer not in the manual?

Higen FDA6000C Series Specifications

General IconGeneral
BrandHigen
ModelFDA6000C Series
CategoryServo Drives
LanguageEnglish

Related product manuals