Installation SmartRadar FlexLine
Part No.: 4417.760_Rev06 Installation Guide
27
4.10.1 Compound Glands
Use explosion proof (Ex-d) compound glands with an appro-
priate IP value.
4.10.2 Conduits
Use explosion proof (Ex-d) conduits with an appropriate IP
value. See the type plate on the device.
CAUTION!
Improper installation of cable glands, conduits, or
stopping plugs will invalidate the Ex approval of the
SmartRadar.
NOTE:
Only for use in ATEX and IEC Ex approved installations.
NOTE:
Install the compound glands according to the instructions
provided by the manufacturer.
WARNING!
If the SmartRadar is installed in a hazardous area:
• Metal conduits must be used, size 3/4”.
• Stopper boxes must be installed within 45 cm (18”) of
the device to seal the cabling in the conduit.
NOTE:
Install the conduits according to the instructions provided
by the manufacturer.