Periphery components for ESSER FACP
TI 798960.GB0 / 04.20 57
9 Alarm devices
Alarm devices can be integrated in IQ8Quad automatic fire detectors (Section 5.3) or used as a stand-alone
alarm device IQ8Alarm Plus on the esserbus
®
PLus of ESSER fire alarm control panels. Conventional alarm
devices (Section 9.2) are connected to the FACP via esserbus
®
transponders.
9.1 Alarm device IQ8Alarm Plus
The devices provide a synchronous visual alarm according to EN 54-23 and an audible alarm according to
EN 54-3.
There is the option to use either the visual or audible alarm separately or to combine both together. The alarms
can be configured to suit the intended application using the tools 8000 service and programming software. Up to
64 IQ8Alarm Plus can be connected to the esserbus
®
PLus loop for ESSER fire alarm control panels. The flat
base is included in the scope of delivery; alternatively, the IP base (806201 / 806202) can be used.
Features
• Device category: W-x-y/O-x-y in accordance with EN 54-23
• Visual alarm with configurable signal range in accordance with EN 54-23
• Variable load factors – for visual and/or acoustic systems, incl. voice
• Acoustic alarm devices according to EN 54-3 with 20 different programmable acoustic signals incl. DIN sound
according to DIN 33404-3
• Acoustic voice signal devices according to EN 54-3 with 5 pre-programmed alarm texts in 5 languages
• Different text components are possible for alarms, evacuation and test alarms
• Simple programming thanks to a uniform programming interface for all alarm devices of the IQ8 system
• Power supply via esserbus
®
PLus
• Up to 64 alarm devices per esserbus
®
PLus
• Each alarm device with integrated isolator
60
A
B
50
A
B
B
B
A
A
78
60
26
93
75
60
112
112
32
Fig. 38: Alarm devices IQ8Alarm +
Fig. 39: Dimensions Dimensions (in mm)
System requirements
• FACP Compact, FACP IQ8Control, FACP FlexES Control (with current software versions)
• FACP with esserbus
®
PLus functionality
• Service and programming software tools 8000