TC · Edition 08.17 26
Function
3.1.7 Test instant for Mode 3: testing before and after
burner run
5s
10s
15s
Mode 3
The first test is carried out before burner run (as with
Mode 1):
The tightness test starts with incoming thermostat/
start-up signal ϑ. If the valves are tight, the LEDs
and
are green. Once the safety interlock input
signal
is active, the OK enable signal is forwarded to
the automatic burner control unit, see page 24 (Test
instant for Mode 1: testing before burner run).
The second test is carried out after burner run (as with
Mode 2):
The tightness test after burner run starts when the
thermostat/start-up signal ϑ drops, see page 25
(Test instant for Mode 2: testing after burner run).