TC · Edition 08.17 45
Technical data
Environment
Gas type and inlet pressure p
u
:
dependent on external pressure switch.
The pressure switch is set to half the inlet pressure p
u
/2.
The switching differential may not exceed ±10% of the
set switching pressure, see page 42 (External pres-
sure switch for TC 4).
Test period t
P
:
TC 4101: 10 to 60 s, adjustable.
Set at the factory to 10 s.
TC 41010: 100 to 600 s, adjustable.
Set at the factory to 100 s.
Ambient temperature: 15 to +60°C
(5 to 140°F), no condensation permitted.
Storage temperature: 15 to +40°C (5 to 10F).
Mechanical data
Enclosure: IP 40.
5 knock-out holes for M16 plastic cable glands.
Screw terminals: 2.5 mm
2
(AWG 14).
Housing made of impact-resistant plastic.
Weight: approx. 400 g (0.88 lbs).