EasyManuals Logo
Home>Honeywell>Controller>Touchpoint Plus

Honeywell Touchpoint Plus User Manual

Honeywell Touchpoint Plus
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Maintenance
MAN0996_Iss 1_02/16 Touchpoint Plus
Pt. No. 3011M5044_EN 46 User Guide
6.2 Routine Testing
It is normal practice to sound the site alarms weekly, both to check they work and to accustom personnel to the sound
they make.
As it involves isolating / inhibiting emergency systems during testing, it might be more prudent to test the TPPL relays and
mA outputs only on a planned monthly basis.
Always have alternative safety arrangements in place and alert your personnel before and during testing.
6.2.1 Exercising the Audio/Visual Alarms
Audio/visual alarms can be tested by switching the Dedicated Alarms On. To do this:
1) Ensure that relay activated output systems (i.e. emergency deluge / sirens etc.) are isolated before starting the test.
2) Login as an Administrator or Service.
3) Touch Menu>System Test >Dedicated Alarm Contacts.
4) Touch the appropriate Alarm to toggle it on for each output (see below).
5) Check the alarm outputs are visible / audible and turn them off when satisfied.
6) Touch [Finish] when the tests are completed and all selections will automatically turn off.
CAUTION
Ensure that the system is returned to normal operation once testing is complete.

Table of Contents

Other manuals for Honeywell Touchpoint Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Touchpoint Plus and is the answer not in the manual?

Honeywell Touchpoint Plus Specifications

General IconGeneral
BrandHoneywell
ModelTouchpoint Plus
CategoryController
LanguageEnglish

Related product manuals