XNX Universal Transmitter Quick Start Guide
13
Single Transmitter Distances
For installations that have dedicated wiring between the transmitter and the
power supply, use the following chart. These distances assume stranded wire is
used.
Single Transmitter Distances
Conguration
18 AWG
[1�0 mm
2
]
16 AWG
[1�5 mm
2
]
14 AWG
[2�0 mm
2
]
12 AWG
[3�5 mm
2
]
XNX mV or EC
With Sensor
1140 feet
[347 meters]
1810 feet
[551 meters]
2890 feet
[880 meters]
4620 feet
[1408 meters]
XNX IR with
Searchpoint Optima Plus
660 feet
[201 meters]
1060 feet
[323 meters]
1690 feet
[515 meters]
2690 feet
[820 meters]
XNX IR with
Searchline Excel
550 feet
[168 meters]
890 feet
[270 meters]
1410 feet
[430 meters]
2260 feet
[690 meters]
NOTE
If multiple transmitters are using the same power supply, make sure the
power supply wattage rating is high enough to power all transmitters
simultaneously.
Daisy-Chained Transmitter Distances
A few selected scenarios are presented here to provide a base to work from.
1. Severaltransmittersequallyspacedfromthemselvesandthepower
source.
2 Transmitters - Distance “d”
Conguration
18 AWG
[1�0 mm
2
]
16 AWG
[1�5 mm
2
]
14 AWG
[2�0 mm
2
]
12 AWG
[3�5 mm
2
]
XNX mV or EC
With Sensor
380 feet
[115 meters]
600 feet
[183 meters]
960 feet
[292 meters]
1540 feet
[469 meters]
XNX IR with
Searchpoint Optima Plus
220 feet
[67 meters]
350 feet
[106 meters]
560 feet
[170 meters]
900 feet
[274 meters]
XNX IR with
Searchline Excel
185 feet
[56 meters]
295 feet
[90 meters]
470 feet
[143 meters]
750 feet