XNX Universal Transmitter Quick Start Guide
58
9.2 ECSensorPerformanceData,FactoryMutualVeried
Gas Cartridge P/N
Selectable Full
Scale Range
(Display and
4-20mA Full
Scale)
Default
Range
Range
Incre-
ments
Lower
Alarm
Limit
Lower
Detec-
tion
Limit
Lower
Explo-
sive
Limit
(% Vol)
Zero
Deviation
Selectable
Cal Gas
Range
Default
Cal Point
Response
Time
(T50) sec
Response
Time
(T90)
sec
Accuracy
Operating Temperature
Operating
Humidity
Min Max
Min
RH
Max
RH
O
2
Oxygen XNXXSO1FM n/a 23.0% Vol n/a 5.0%Vol 5% Vol n/a n/a
20.9 %Vol
(fixed)
20.9 %Vol T20 <10 <30 <+/-0.5 %Vol
-30°C /
-34°F
55°C /
131°F
15% 90%
H
2
S Hydrogen Sulfide XNXXSH1FM 10.0 to 50.0 ppm 15.0 ppm 0.1 ppm 5.0 ppm 1.5 ppm n/a -2.5 ppm
30 to 70%
of the
selected
full scale
range
10 ppm <20 <30
2 ppm or 10% of
reading, whichever
is greater
-40°C /
-40°F
55°C /
131°F
15% 90%
CO Carbon Monoxide XNXXSC1FM
1
100 to 1000 ppm 300 ppm 100 ppm 30 ppm 15 ppm na/ -25 ppm 100 ppm <15 <30 See footnote 1
-40°C /
-40°F
55°C /
131°F
15% 90%
Footnotes:
1. 1. XNXXSC1FM accuracy over temperature <±10% of reading 20°C/68°F to 55°C/131°F, <±20% of reading 20°C/68°F to -10°C/14°F, <±30% of reading -10°C/14F to -20°C/-4°F.
Recalibration is recommended if the temperature of the local environment has varied by more than -30°C.
Notes:
Performance gures are measured by test units calibrated at 50% of full scale, at ambient conditions of 20°C, 50% RH, with the EC weatherproof cover attached
IP rating of FM Cartridges is IP63.
Barometric pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0.1% change of output per % change in pressure. When the barometric
pressure changes by ±20% the output from the O
2
sensor changes <±0.4%Vol. However, the oxygen sensor shows transient behavior when subjected to a rapid change in ambient
pressure due to either weather or altitude. For example, a 10KPa instantaneous positive pressure step change may cause an overscale alarm condition for a period of about 12
seconds.
Operating the XNX EC sensor at extended temperature ranges for a prolonged time period exceeding 12 hours my cause deterioration in the sensor performance and shorten
sensor life. Extended temperature range for XNX EC sensors is -40°C ot -20°C.
Response times may increase at lower temperatures.
Contact Honeywell Analytics for additional data or details.

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
BrandHoneywell
ModelXNX
CategoryTransmitter
LanguageEnglish

Related product manuals