XNX Universal Transmitter Quick Start Guide
22
4.6.1 XNX Electrochemical (EC) Sensor Installation
CAUTION
For biased sensors (e.g. Nitrogen Dioxide) remove the sensor stabilizer from the bottom of the
sensor prior to installation.
UsingFigure11asaguide,followtheprocedurebelow:
1. Checkthatthelabelonthenewsensoristhecorrectgastype.
2. Unscrewtheweatherproofcover,loosentheretainerlockingscrew
withthesuppliedhexkeyandunscrewthesensorretainer.
3. Pluginthenewsensortakingcaretoalignthesensorpinswiththe
connector.
4. Retthesensorretainer,tightenthelockingscrewwiththesupplied
hexkeyandrettheweatherproofcover.
5. Countdowntimeofupto180seconds(dependentonsensortype)is
displayed.
6. Acknowledgementofthegastypewillberequiredbefore
proceeding.Formoreinformationonsettinggastype,seetheXNX
TechnicalManualSection2.51GasSelection.
7. Afterthesensorisinstalledandthegastypeisconrmed,the
Range,alarmlevelsandotherimportantsettingsmustbeset;see
appropriatesectioninSection6-PoweringtheXNXfortheFirst
Time.
8. OncetheXNXhasbeencongured,calibratethedetectorfollowing
theproceduresinSection8.1-Calibration.
Transmitter
Sensor Retainer &
Locking Screw
2
1
3
4
5
New Sensor
Weatherproof Cap
Figure 11. Installing the plug-in sensor

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
BrandHoneywell
ModelXNX
CategoryTransmitter
LanguageEnglish

Related product manuals