XNX Universal Transmitter Quick Start Guide
62
10 XNX Catalytic Bead and IR Replacement Sensor Cartridges
Sensor
Type
1, 2
Target Gas
Cartridge
Part No
Operating
Pressure
Range
(kPa)
Operating
Humidity
Range (%
RH non-
condensing)
Air
Speed
(m/s)
Maximum
Range
Selectable Range
3
Increment
Default
Range
Cal Gas Range
Cal Gas
P/N
Cal Gas Description
MPD-IC1 Carbon Dioxide 1226-0301 80 - 110 0 - 95 0 - 6 5.00 %Vol 1.00 to 5.00 %Vol 1.00 %Vol 5.00 %Vol 1.50 to 3.5 %Vol Contact HA 2.5 %VOL CO
2
in Air
MPD-IV1 Methane 1226-0299 80 - 110 0 - 95 0 - 6 5.00 %Vol 1.00 to 5.00 %Vol 1.00 %Vol 5.00 %Vol 1.50 to 3.5 %Vol GFV352 2.5 %VOL CH
4
in Air
MPD-IF1 Flammables 1226-0300 80 - 110 0 - 95 0 - 6 100 %LEL 20 to 100 %LEL
3
10 %LEL 100 %LEL 30 to 70 %LEL GFV406 1 %VOL C
3
H
8
in Air
MPD-CB1 Flammables 1226A0359 80 - 120 see footnote 4 0 - 6 100 %LEL 20 to 100 %LEL
3
10 %LEL 100 %LEL 30 to 70 %LEL GFV352 50 %LEL CH
4
in Air
1
Agency approved hydrogen sensors are MPD-CB1 and 705 STD.
2
When ordering replacement MPD sensor cartridges, the replacement cartridge must be the same type as factory congured. Substituting a different cartridge will void agency certication.
3
On XNX %LEL units carrying UL/CSA/FM certications, the range is xed at 100%LEL and is not adjustable.
4
Humidity: 0% to 99% RH non-condensing

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
BrandHoneywell
ModelXNX
CategoryTransmitter
LanguageEnglish

Related product manuals