FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
155
Figure 5-50 Removing a CIM (from a battery cabinet)
Figure 5-51 Removing a CIM (from a battery rack)
The preceding text describes how to remove a CIM from the top of the BCB box. The method gives a
reference for removing a CIM from the side panel of the BCB box.
2. Record the DIP switch address of the CIM.
Step 4 Install the new CIM.
1. Clamp the CIM to the fastener.
2. Set the DIP switch for the CIM based on the recorded information.
Step 5 Reconnect cables to the CIM based on the cable labels.
Step 6 After the installation, set up the network. For details, see iBAT 2.0-CIM01C2 User Manual.
----End
5.4.2 Replacing the BIM
Prerequisites
A BIM needs to be replaced.
A spare BIM of the same model is available and functional.