FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
2 Routine Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
Maintenance
Item
Maint
enanc
e
Interv
al
Operation
Guide
Expected
Result
Exception Handling
the PDC
y
observation
rodent
movements
in the PDC.
professional for advice.
PDC
component
appearance
Quarter
ly
Visual
observation
The exterior
is intact.
Take measures depending
on the severity.
Operating
temperature
and humidity of
the PDC
Quarter
ly
Point
thermometer
Operatin
g
temperat
ure:
10°C to
+55°C
Humidity
:
5%95%
RH
Check whether the air
conditioner and
dehumidifier in the
equipment room function
properly.
PDC interior
Yearly
Check whether
dust has
accumulated on
the PDC
mounting
panels.
The white
paper that
you use to
wipe the
mount panel
is clean.
If the white paper becomes
dirty, clean the PDC
interior.
Oxidation of
metal
components in
the PDC
Yearly
Visual
observation
No metal
component
rusts.
If any metal component
suffers from severe
oxidation, remove the
rust or replace the
component in a timely
manner.
If the component is
painted, repaint it after
removing the rust.
2.3.2 Integrated UPS Routine Maintenance
2.3.2.1 Routine Maintenance for UPSs

Table of Contents

Other manuals for Huawei FusionModule5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule5000 and is the answer not in the manual?

Huawei FusionModule5000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule5000
CategoryWireless Router
LanguageEnglish

Related product manuals