FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Check the
operating
temperature and
humidity of the
new main way.
Point
thermometer
and T/H sensor
Operating
temperatu
re: –10°C
to +55°C
Humidity
:
5%–95%
RH
Check whether the air
conditioner and dehumidifier
in the equipment room
function properly.
Check the dust
on the face of
the new main
way.
The piece of
white paper
that you use
to wipe the
cabinet panel
is clean.
If the piece of white paper
turns black, clean the new
main way.
Check the
oxidation of
metal
components in
the new main
way.
No metal
component
rusts.
If any metal component
experiences severe
oxidation, remove the
rust or replace the
component in a timely
manner.
If the component was
painted before, repaint it
after removing the rust.
2.4 Routine Maintenance for the Cooling System
Table 2-12 describes the routine maintenance requirements for the NetCol5000-C.
The condensate pump, float, electric heater, and humidifier are optional components. If not configured,
ignore the maintenance for them.
If the NetCol5000-C will be idle for a long time in the low temperature area, switch off the
chilled water stop valve and humidifier water inlet valve to prevent freezing.