FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
2 Routine Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
Table 2-12 Routine maintenance
No.
Operation
Troubleshooting
Period
Result
1
Check whether an air
filter is blocked.
Clean (water can be used) or
replace the air filter.
Monthl
y
□Passed.
□Failed.
2
Check whether an air
filter is damaged or
deformed.
Replace the air filter by referring
to 5.2.3 Replacing an Air Filter if
necessary.
Monthl
y
□Passed.
□Failed.
3
Check that the valve
does not leak.
Shut down the exhaust valve.
Monthl
y
□Passed.
□Failed.
4
Check that screws
fastening the condensate
pump and water sensor
are securely connected.
Secure the screws tightly.
Monthl
y
□Passed.
□Failed.
5
Check that the water pan
filter is clean and not
blocked.
Clean the water pan filter, shown
in Figure 2-1.
Monthl
y
□Passed.
□Failed.
6
The humidifier cylinder
interior wall is free from
layered water scale.
Replace the humidifier cylinder
by referring to 5.2.7 Replacing a
Humidifier Cylinder. Huawei
recommends replacing the
humidifier cylinder once every
six months.
Monthl
y
□Passed.
□Failed.
7
The electric heater
surface is not eroded,
dirtied, or blocked.
Replace the electric heater by
referring to 5.2.6 Replacing an
Electric Heater.
Monthl
y
□Passed.
□Failed.
8
Humidity and
temperature sensors in
air conditioners and
aisles are securely
installed.
Secure the sensors.
Monthl
y
□Passed.
□Failed.
9
Lift the low float and
tap Running >
Status on the
controller LCD. If
the float is in the ON
state, it is working
properly. Five
seconds later one
condensate pump
would start. Put
down low float.
Lift the low and high
float. Tap
Running > Status
on the controller
LCD. If the floats are
in the ON state, they
If the float is faulty, replace it
promptly. For details, see
5.2.13 Replacing a Float.
If the condensate pump is
faulty, replace it promptly.
For details, see 5.2.4
(Optional) Replacing a
Condensate Pump.
Top
drainag
e:
monthly
Bottom
drainag
e:
Quarterl
y
□Passed.
□Failed.

Table of Contents

Other manuals for Huawei FusionModule5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule5000 and is the answer not in the manual?

Huawei FusionModule5000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule5000
CategoryWireless Router
LanguageEnglish

Related product manuals