No.
Operation
Troubleshooting
Period
Result
21
Check whether the
display panel, humidity
and temperature sensor
or cables is aging on the
surface.
Replace the components or
cables.
Semi-an
nual
□Passed.
□Failed.
22
Use a high-precision
humidity and
temperature sensor to
calibrate the humidity
and temperature sensors
inside and outside the
cabinet.
If the temperature deviation is
greater than 1°C or humidity
deviation is greater than 5%, the
temperature and humidity sensor
must be calibrated or replaced.
Semi-an
nual
□Passed.
□Failed.
23
The heat exchanger fins
are not pushed down.
Use a fin brush to organize the
fins that are pushed down.
Semi-an
nual
□Passed.
□Failed.
Figure 2-1 Removing the water pan filter

Table of Contents

Other manuals for Huawei FusionModule5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule5000 and is the answer not in the manual?

Huawei FusionModule5000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule5000
CategoryWireless Router
LanguageEnglish

Related product manuals