FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
al
3.1.3 Power Distribution Unit Alarm Reference
Alarm ID
Alarm Name
Alarm
severity
Possible
Cause
Solution
0x5001
Communication
failure
Critical
Communication
with the PoE
module is
interrupted.
Check the cable
connection to
the power
distribution
unit.
0x5010
First output
overloaded
Major
The output of
the first branch
is overloaded or
the power
supply pin of
the first branch
is
short-circuited.
1. Check that
the first
output is not
overloaded.
2. Check that
the power
supply pin
of the first
branch is not
short-circuit
ed.
0x5011
Second output
overloaded
Major
The output of
the second
branch is
overloaded or
the power
supply pin of
the second
branch is
short-circuited.
1. Check that
the second
output is not
overloaded.
2. Check that
the power
supply pin
of the
second
branch is not
short-circuit
ed.
0x5012
Third output
overloaded
Major
The output of
the third branch
is overloaded or
the power
supply pin of
the third branch
1. Check that
the third
output is not
overloaded.
2. Check that
the power

Table of Contents

Other manuals for Huawei FusionModule5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule5000 and is the answer not in the manual?

Huawei FusionModule5000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule5000
CategoryWireless Router
LanguageEnglish

Related product manuals