Detailed Function Description
69
Figure 6.17 Relationship between AI and corresponding setting.
Function
Code
Name Description Setting Range
Factory
Setting
P5.20 AI2 lower limit 0.00V~10.00V 0.00~10.00 0.00V
P5.21
AI2 lower limit
corresponding setting
-100.0%~100.0% -100.0~100.0 0.0%
P5.22 AI2 upper limit 0.00V~10.00V 0.00~10.00 5.00V
P5.23
AI2 upper limit
corresponding setting
-100.0%~100.0% -100.0~100.0 100.0%
P5.24 AI2 filter time constant 0.00s~10.00s 0.00~10.00 0.10s
P5.25 AI3 lower limit -10.00V ~10.00V -10.00~10.00 0.00V
P5.26
AI3 lower limit
corresponding setting
-100.0%~100.0% -100.0~100.0 0.0%
P5.27 AI3 upper limit -10.00V ~10.00V -10.00~10.00 10.00V
P5.28
AI3 upper limit
corresponding setting
-100.0%~100.0% -100.0~100.0 100.0%
P5.29 AI3 filter time constant 0.00s~10.00s 0.00~10.00 0.10s
P5.30 AI4 lower limit 0.00V~10.00V 0.00~10.00 0.00V
P5.31
AI4 lower limit
corresponding setting
-100.0%~100.0% -100.0~100.0 0.0%
P5.32 AI4 upper limit 0.00V~10.00V 0.00~10.00 10.00V
P5.33
AI4 upper limit
corresponding setting
-100.0%~100.0% -100.0~100.0 100.0%
P5.34 AI4 filter time constant 0.00s~10.00s 0.00~10.00 0.10s