Detailed Function Description
74
These parameters determine the relationship between analog output voltage/current and
the corresponding output value. When the analog output value exceeds the range
between lower limit and upper limit, it will output the upper limit or lower limit.
When AO is current output, 1mA is corresponding to 0.5V.
For different applications, the corresponding value of 100.0% analog output is different.
For details, please refer to description of each application.
Figure 6.18 Relationship between AO and corresponding setting.
Function
Code
Name Description Setting Range
Factory
Setting
P6.18 HDO lower limit 0.0%~100.0% 0.0~100.0 0.0%
P6.19
HDO lower limit
corresponding output
0.0 ~ 50.0kHz 0.0~50.0 0.0kHz
P6.20 HDO upper limit 0.0%~100.0% 0.0~100.0 100.0%
P6.21
HDO upper limit
corresponding output
0.0 ~ 50.0kHz 0.0~50.0 50.0kHz
The description of P6.18~P6.21 is similar to AO.