Detailed Function Description
71
6.7 P6 Group -- Output Terminals
Function
Code
Name Description
Setting
range
Factory
Setting
P6.00
HDO
selection
0: High-speed pulse output
1: ON-OFF output
0~1 0
0: High-speed pulse output: The maximum pulse frequency is 50.0 kHz. Please refer to
description of P6.09.
1: ON-OFF output: Please refer to description of P6.03.
Notice: The output of HDO terminal is multi-function ON-OFF output.
Function
Code
Name Description
Setting
Range
Factory
Setting
P6.01 Y1 output selection
Open-collector
output
0~31 1
P6.02 Y2 output selection
Open-collector
output
0~31 0
P6.03
HDO ON-OFF
output selection
Open-collector
output
0~31 0
P6.04
Relay 1 output
selection
Relay output 0~31 3
P6.05
Relay 2 output
selection
Relay output 0~31 0
P6.06
Relay 3 output
selection
Relay output 0~31 0
OC/Relay output functions are indicated in the following table:
Setting
Value
Function Description
0 No output Output terminal has no function.
1 Run forward ON: During forward run.
2 Run reverse ON: During reverse run.
3 Fault output ON: Inverter is in fault status.
4 Motor overload Please refer to description of PB.04~PB.06.
5 Inverter overload Please refer to description of PB.04~PB.06.
6 FDT reached Please refer to description of P8.25, P8.26.