Detailed Function Description
80
For details, please refer to description of P0.11 and P0.12.
Function
Code
Name Description Setting Range
Factory
Setting
P8.06
Jog reference 0.00~P0.07 0.00~ P0.07 5.00Hz
P8.07
Jog acceleration time
0.0~3600.0s
0.0~3600.0 20.0s
P8.08
Jog deceleration time
0.0~3600.0s
0.0~3600.0 20.0s
The meaning and factory setting of P8.07 and P8.08 is the same as P0.11 and P0.12. No
matter what the value of P1.00 and P1.08 are, jog will start as start directly mode and
stop as deceleration to stop mode.
Function
Code
Name Description Setting Range
Factory
Setting
P8.09
Skip frequency 1 0.00~P0.07 0.00~P0.07 0.00Hz
P8.10
Skip frequency 2 0.00~P0.07 0.00~P0.07 0.00Hz
P8.11
Skip frequency
bandwidth
0.00~P0.07 0.00~P0.07 0.00Hz
By means of settinzg skip frequency, the inverter can keep away from the mechanical
resonance with the load. P8.09 and P8.10 are centre value of frequency to be skipped.
Notice:
z If P8.11 is 0, the skip function is invalid.
z If both P8.09 and P8.10 are 0, the skip function is invalid no matter what
P8.11 is.
z Operation is prohibited within the skip frequency bandwidth, but changes
during acceleration and deceleration are smooth without skip.
The relation between output frequency and reference frequency is shown in
following figure.
Figure 6.20 Skip frequency diagram.