6.6.4 Circuit example for the master-slave operation with AIC/LCL lter and common mode lter
-Q1
-F1
L1
L2
L3
-F5
-K2
1) U V W
PE
-U5
-U1
-U3
-K3
U1.2
V1.2
W1.2
U1.3
V1.3
W1.3
+UZK -UZK
L1 L2 L3
-S6
°C
T1 T2 KTY+ KTY-
+
KTY
L N PE
N
V W
PE
-U6
-U2
-U4
-K4
U1.2
V1.2
W1.2
U1.3
V1.3
W1.3
+UZK
-UZK
L1 L2 L3
-S6
°C
T1 T2 KTY+ KTY-
+
KTY
L N PE
-F3
U V T1 T2WPE
-U7
+PA
-
L1
L2
L3
Master
U V T1 T2WPE
-U8
+PA
-
L1
L2
L3
Slave
T1 T2U V W PE
-U9
+
-
-S7
-G1
Rv1
Rv2
-F6
-F7
-F8
-F9
-F2 -F4
1) U
Legend
Q1 Main switch G1 Motor
F1, F2 Main fuses
2)
S6
Temperature detection NC contact and KTY84
sensor
3)
F3, F4 Fan fuse S7 Motor temperature switch
F5 Pre-charging fuses 20 A (slow) U3, U4 Commonmodelter
F6, F7
F8, F9
DC fuses
2)
U7,
U8
COMBIVERT F5-AIC
K3, K4 Main contactor U9 Drive converter
K2 Pre-charging contactor
U5, U6 LCLlter
Rv1, Rv2 Pre-charging resistors
U1, U2 EMClter(integratedintoU4uptosize24)
Fan control => Programming manual
Figure 11: Circuit example for the master-slave operation with AIC/LCL lter and common mode lter
1)
Output terminals U, V, W for size 26 and 29 => U2, V2, W2
2)
Mains and DC fuses must be monitored.
3)
Design dependent on lter size. Attention, observe polarity !
46
CONNECTION OF THE COMBIVERT F5-AIC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT 24F5 Series and is the answer not in the manual?

KEB COMBIVERT 24F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT 24F5 Series
CategoryInverter
LanguageEnglish

Related product manuals