6 Commissioning
Factory setting of the shutdown limit for O
2
monitoring with active CO control = 0.4 vol.%.
Checking the O
2
effect
1. Run to the shut-off limits
2. Check the correction influence
NOTICE
If the factory-set switch-off limit of 0.4 vol.% O
2
is too low for the application, it can be raised
using the CMS Remote Software (AL4). If necessary, contact LAMTEC Support:
support@lamtec.de
+49 (0) 6227 6052-33
’How to’ see chapter 6.3.4.1 Run to Shut-off Limits