The integrated ignition control board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed
below in table 4.
TABLE 4
DIAGNOSTIC CODES
Make sure to Identify LED’S Correctly..
LED#1
32M88 − DS1 Green
78M47 − DS1 Red
LED #2
32M88 − DS2 Green
78M47 − DS2 Green
DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
SLOW FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
SIMULTANEOUS
FAST FLASH
SIMULTANEOUS
FAST FLASH
Normal operation − signaled when heating demand initiated at thermostat.
SLOW FLASH ON
Primary or secondary limit switch open. Limit must close within 3 minutes or
unit goes into 1 hour Watchguard.
OFF SLOW FLASH
Prove switch open.
OR:Blocked inlet/exhaust vent;
OR: Prove switch closed prior to activation of combustion air inducer.
ALTERNATING
SLOW FLASH
ALTERNATING
SLOW FLASH
Watchguard −− burners failed to ignite
OR: limit open more than 3 minutes (control board 32M88 Only)
OR: lost flame sense 5 times in one heating cycle
OR: prove switch opened 5 times in one heating cycle
SLOW FLASH OFF Flame sensed without gas valve energized.
ON SLOW FLASH Rollout switch open. OR: 12-pin connector improperly attached.
ON ON
ON OFF
Circuit board failure or control wired incorrectly.
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH
Low flame signal. Measures below
Control board 32M88 − 0.18 microamps
Control board 78M47 & 100973−01 − 1.5 microamps
Replace flame sense rod.
ALTERNATING
FAST FLASH
ALTERNATING
FAST FLASH
The following conditions are sensed
Improper main ground (control board 32M88) during the ignitor warm−up period
ONLY Improper main ground (control board 78M47 & 100973−01) continuously
OR: Broken ignitor (control board 32M88)
OR: Open ignitor circuit (control board 32M88)
OR: Line voltage to control below
Control board 32M88 75V
Control board 78M47 & 100973−01 90V
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Low flame sense current = SureLight Control Board 32M88 0.16 − 0.17 microamps Ignition Control Board 78M47 & 100973−01 0.5 − 1.4 microamps
FIGURE 5
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
IGNITOR**
15 Sec.
Pre −Purge
20 sec.
Ignitor Warmup
4 Sec.Trial
for Ignition
Post
Purge
5 SEC
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
INDOOR BLOWER
Blower On"
Delay
End of
Heat Demand
Blower
Off
Time
** Ignitor on ignition control board 78M47 & 100973−01 equipped units will energize for the first 3 seconds of the 4
second trial, following the ignitor 20 second warm up .