COOLING SEQUENCE OF OPERATION
SureLight Control Board 32M88
NORMAL COOLING MODE ABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
SIGNAL POLARITY REVERSED AT LED.
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
IS POLARITY REVERSED?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
CHECK FOR MAIN BURNER FLAME SENSE.
IS MAIN BURNER FLAME OFF?
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED ON COOLING SPEED.
ELECTRONIC AIR CLEANER ENERGIZED.
COMPRESSOR OFF.
THERMOSTAT OPENS.
SYSTEM FAN OFF
WITH 0-SECOND DELAY. ELECTRONIC
AIR CLEANER DE−ENERGIZED.
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
SIGNAL ROLL-OUT SWITCH OPEN AT LED.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL UNWANTED FLAME SENSED AT LED.
SEQUENCE HOLDS UNTIL FLAME IS NOT SENSED.
LED SIGNALS WAITING ON CALL FROM
THERMOSTAT. CONTROL WILL NOT RESPOND
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
YES
YES
YES
NO
NO
NO
IS VOLTAGE
HIGH ENOUGH?
75 VOLTS

Table of Contents

Other manuals for Lennox G43UF SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G43UF SERIES and is the answer not in the manual?

Lennox G43UF SERIES Specifications

General IconGeneral
BrandLennox
ModelG43UF SERIES
CategoryFurnace
LanguageEnglish

Related product manuals