EasyManuals Logo
Home>Lennox>Control Systems>Harmony III

Lennox Harmony III User Manual

Lennox Harmony III
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11
PIAB = [(Required CFM - Minimum CFM) / (Maximum CFM - Minimum CFM)] * 100
Sample CFM
RequiredMinimum Maximum Minimum
Sample PIAB = ([___920 -450 ] / [ 2000 -450 ]) x 100
==
Sample PIAB =([ 470 ] / [1550]) x 100
=
Sample PIAB =[0.303] x 100 = 30 %
Figure 10. PIAB Calculation Example
example
example
CFM
CFM
values
values
Require
Require
d
d
CF
CF
M
M
CFM
CFM
Zon
Zon
e
e
1
1
Zone
Zone
2
2
Zone
Zone
3
3
Zone
Zone
4
4
Min.
Min.
Max.
Max.
1020
1020
1500
1500
720
720
OFF
OFF
720
720
2200*
2200*
*High cool jumper settin
*High cool jumper settin
g
g
PIA
PIA
B
B
formula
formula
100
100
(R
(R
e
e
q’
q’
d
d
CFM
CFM
min. C
min. C
FM
FM
)
)
(Max. CFM
(Max. CFM
min. CFM
min. CFM
)
)
x
x
U
U
s
s
i
i
ng e
ng e
x
x
a
a
m
m
p
p
l
l
e v
e v
a
a
lue
lue
s
s
abo
abo
v
v
e,
e,
fi
fi
nd
nd
PIAB
PIAB
f
f
o
o
r
r
Zone 1
Zone 1
:
:
PIA
PIA
B
B
(
(
1
1
02
02
0
0
-
-
7
7
2
2
0
0
)
)
= 30
= 30
0
0
=.20
=.20
.
.
.
.
.
.
.
.
..
..
.
.
..
..
.
.
.
.
.
.
..
..
.
.
.
.
.
.
.
.
.
.
...
...
.
.
..
..
.
.
..
..
.
.
(2220 - 720) =150
(2220 - 720) =150
0
0
.
.
.
.
.
.
.
.
..
..
.
.
..
..
.
.
.
.
.
.
..
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
PIAB Jumper setting
PIAB Jumper setting
%
%
.20 x 10
.20 x 10
0
0
20%
20%
.
.
.
.
.
.
.
.
..
..
.
.
.
.
.
.
..
..
.
.
.
.
...
...
.
.
..
..
.
.
Figure 11. Determine PIAB Jumper Settings
1.10.6. Continuous Air Reduction Jumpers
During continuous fan mode without either a heating or cooling demand, the blower
runs at the total percentage of the CFM jumper settings of the zones calling for
continuous fan (not to exceed 100% of blower capacity). A continuous air reduction
jumper allows the blower speed to be reduced by a percentage during continuous
fan mode.
The selections are 75%, 50%, 25% and 0%. At the factory, the jumper is set on
0%. Set the jumper to the position equal to the amount of continuous air reduction
desired.
NOTE: If the calculations using a reduction percentage indicated a resulting CFM
lower than the blower’s minimum CFM rating, the blower will deliver its
minimum CFM
1.10.7. Heating Air Reduction Jumpers
NOTE: For heat pump applications, ALWAYS set the jumper on 0%. High head
pressures may result if air is reduced during heating mode.
NOTE: For use in warm-climate areas where units have high cooling capacity with
low heat capacity, ALWAYS set the jumper on 0%.
The heating air reduction jumper enables the blower speed, during heating only, to
run at a reduced rate compared to the cooling blower speed.
The selections are 40%, 20% and 0%. Jumpers are set to 0% from the factory.
Set the jumper to the position equal to the amount of heating air reduction desired.
CONTINUOUSHEATING
0%
20%
40%
75%
50%
0%
25%
factory
settings
shown
heating jumper
Must be set on 0%
for heat pump
application
Figure 12. Heating Air Reduction Jumpers
1.10.8. Heat/Cool Staging
Heating/Cooling staging jumpers prevent any rapid staging of the equipment. This
section shows the recommended settings for heating/cooling staging temperatures
andexplainsthetemperaturedifferentialsfordifferentequipmentcongurations.
In the diagrams, sine waves indicate which stage operates during the rise and
fall of discharge air temperature for the different heating/cooling staging jumpers.
Recommended jumper settings are shown in bold type.
1.10.8.1. Heating Staging Temperature Jumper
Heating Staging temperature jumpers are used to set the temperature at which the
secondstageheatingequipmentcomesON.Itsselectionsrangefrom85-130(°F).
Thesettinghasabuilt-indifferentialof20°F(exceptasdescribedwhen140DAS
jumper is used). During operation, when the discharge air temperature falls below
the jumper setpoint, 2nd-stage heating begins. If the discharge air temperature
reaches the differential temperature, 2nd-stage operation ceases and 1st-stage
heating resumes until the temperature again falls below the jumper set point.
NOTE: For SLP98 furnaces only, the furnace ignition control will automatically
adjust ring rate without a second stage heat demand to match the blower
airow (CFM) requested by the Harmony III zoning system.
HeatPump(range:85-110°F,recommended:90).Themaximumdischargeair
temperatureatwhichtheheatpump/electricheatisallowedtorunisxedat135°F.

Table of Contents

Other manuals for Lennox Harmony III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Harmony III and is the answer not in the manual?

Lennox Harmony III Specifications

General IconGeneral
BrandLennox
ModelHarmony III
CategoryControl Systems
LanguageEnglish

Related product manuals