28
furnace looks at air volume and determines proper ring rate based on DIP
switch 14-19 settings. See SLP98 Installation Instructions for adjustment
options.
3.3.2. Integrated Furnace Control W2 terminal to Harmony III
zoning system Control
SincethefurnaceautomaticallyadjustsringratetomatchCFMtoachieveatarget
temperature rise, connection of Harmony III zoning system control to W2 terminal
on the integrated control is not required.
With W2connected,lowerringratescanbeusedforW1 demand usually resulting
in greater comfort levels per zone. If temperature cannot be maintained, then W2
willquicklyincreaseringratestosatisfydemand.
If discharge air temperature is too low, the integrated control W2 can be connected
toHarmonyIIIzoningsystemcontroltocausethefurnacetoincreaseringrate.
Every two minutes, the integrated control looks at W2. If W2isON,theringrate
increasesby5%.This5%increaseisaddedtothedesiredringrateasdetermined
bythePWM.Therefore,ifa50%dutycyclecorrespondstoa70%ringrate,after
2 minutes of W2,thatsame50%dutycyclewillcorrespondtoa75%ringrate.
This will last for the remainder of the heat cycle.
When W2goesfromONtoOFF,theintegratedcontroldecreasestheringrate
by 5%.
3.3.3. Installation Setup Worksheets
3.3.3.1. SLP98V — Cooling/Heating (Non-Heat Pump Applications)
Job Name:
Indoor Unit Model:
Outdoor Unit Model:
Indoor Unit Setup:
√Cuton-boardlinkW914DEHUMORHARMONY(RtoDS)onfurnaceIFCcontrol(ifnotcut,fuse
will blow in Harmony III zoning system control board)
√W2connectionfromHarmonyIIIzoningsystemtoSLP98isoptional–seeHarmonyIIIzoning
system / furnace installation instructions for details
√DIPswitchsettings(ONorOFF):
DIPSwitch ON or OFF Condition
1 OFF
DIP switch 1 – leave at factory setting – ignored by Harmony
III zoning system
2 OFF
DIP switch 2 – leave at factory setting – ignored by Harmony
III zoning system
3 OFF
DIP switch 3 – leave at factory setting – ignored by Harmony
III zoning system
4 ON
DIP switches 4 and 5 determine heating blower “off” delay –
recommended 180 seconds
5 ON
Job Name:
Indoor Unit Model:
Outdoor Unit Model:
Indoor Unit Setup:
√Cuton-boardlinkW914DEHUMORHARMONY(RtoDS)onfurnaceIFCcontrol(ifnotcut,fuse
will blow in Harmony III zoning system control board)
√W2connectionfromHarmonyIIIzoningsystemtoSLP98isoptional–seeHarmonyIIIzoning
system / furnace installation instructions for details
√DIPswitchsettings(ONorOFF):
6 OFF
DIP switches 6 and 7 – leave at factory setting – ignored by
Harmony III zoning system
7 OFF
8
DIP switches 8 and 9 – cooling blower speed – determines
maximum system CFM – see G71MPP blower tables)
9
10
DIP switches 10 and 11–cooling blower adjust–determines
maximum system CFM – see G71MPP blower tables
11
12 OFF
DIP switches 12 and 13 – leave at factory setting – ignored
by Harmony III zoning system
13 OFF
14 OFF DIPswitches14,15,and16–setslowre,minimumcapacity,
ringrate-DEFAULTSETTINGSHOWNandIS
RECOMMENDED STARTING POINT– see Harmony III
zoning system/furnace install instruction
15 OFF
16 OFF
17 OFF
DIPswitches17,18and19–setshighre,100%
capacity,ringrate-DEFAULTSETTINGSHOWNandIS
RECOMMENDED STARTING POINT– see Harmony III
zoning system/furnace install instruction
18 OFF
19 OFF