Parameter setting with the E82ZBC keypad
Vector control
8
Commissioning
8.4
8.4.2
L
8.4-3
EDS82EV903-1.0-11/2002
8.4.2 Vector control
The following instructions apply to controllers equipped with a standard-I/O
function module and a three-phase AC motor which has been selected
accordingly.
Switch-on sequence Comment
1. Attach the keypad
2. Ensure that controller inhibit is active after mains connection.
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in “Disp” mode after approx. 2 s and indicates the
output frequency (C0050)
PS
mno
p
qr
Hi
Hz
Lo
The menu USEr is active
5. Change to the menu ALL
6. Change to the f mode to configure the basic settings for your
drive
Hi
Hz
Lo
PS
Blinking on the display: 0001
7. Adapt the t e rminal configuration to the wiring (C0007)
Lenze setting: 0, i. e.
E1: JOG1/3 f ixed setpoint selection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW operation
z
y
wx
PS
mno
p
qr
Hi
Hz
Lo
8. Set the minimum output fre quency (C0010)
Lenze setting: 0.00 Hz
[f]
C0011
9. Set the ma ximum output fre quency (C0011)
Lenze setting: 50.00 Hz
0%
100 %
C0010
10. Set the acceleration time T
ir
(C0012)
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
= t
ir
⋅
C0011
f
2
− f
1
.
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
if
= t
if
⋅
C0011
f
2
− f
1
.
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
t
if
= deceleration time wanted
12. Activate the control mode ”vector control” (C0014 = 4)
Lenze setting: Linear V/f characterisitic control (C0014 = 2)
PS
mno
p
qr
Hi
Hz
Lo
z
y
wx
13. Adapt the voltage/current range t o the a nalog setpoint (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
wx
PS
mno
p
qr
Hi
Hz
Lo
Set the DIP switch on the standard-I/O to the s ame
range (see Mounting Instructions for the
standard-I/O)
14. Enter the motor data See motor nameplate
A) Rate d motor speed (C0087)
Lenze setting: 1390 rpm
B) Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor connection type
(star/delta) selected!
C) Rated moto r fre quency (C0089)
Lenze setting: 50 Hz
D) Rated mot o r voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor connection type
(star/delta) selected!
E) Motor-cosϕ (C0091)
Lenze setting: Depending on the controller