Function library
Function blocks
3.5.55 CW/CCW/QSP linking (R/L/Q)
3−245
l
EDSVS9332P−EXT DE 2.0
3.5.55 CW/CCW/QSP linking (R/L/Q)
Purpose
The FB provides a fail−safe connection for the selection of a rotation direction and the QSP function.
C0889/2
C0889/1
R/L/Q
R/L/Q-QSP
R/L/Q-R/L
R/L/Q-R
R/L/Q-L
C0885
C0886
Fig. 3−193 CW/CCW/QSP linking (R/L/Q)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
R/L/Q−R d C0889/1 bin C0885 2 51
R/L/Q−L d C0889/2 bin C0886 2 52
R/L/Q−QSP d
R/L/Q−R/L d
Function
l After mains connection and simultaneous HIGH level at both inputs, the outputs are set as
follows:
Inputs Outputs
R/L/Q−R R/L/Q−L R/L/Q−R/L R/L/Q−QSP
1 1 0 1
l The following truth table results if one of the inputs is set to LOW once after mains connection:
Inputs Outputs
R/L/Q−R R/L/Q−L R/L/Q−R/L R/L/Q−QSP
0 0 0 1
1 0 0 0
0 1 1 0
1 1 unchanged unchanged
l If both inputs are set to HIGH during operation, the values at both outputs remain unchanged.