Function library
Function blocks
3.5.5 Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)
3−102
l
EDSVS9332P−EXT DE 2.0
3.5.5 Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)
Purpose
These function blocks are the interface for analog signals as the
l setpoint input,
l actual value input and
l parameter control.
C0034
1
2
AIN1
+
+
AIN1-OUT
AIN1-GAIN
AIN1-OFFSET
C0404/1
C0404/2
C0402
C0403
C0400
Fig. 3−47 Analog input via terminal X6/1, X6/2 (AIN1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
AIN1−OFFSET a C0404/1 dec [%] C0402 1 19502 −
AIN1−GAIN a C0404/2 dec [%] C0403 1 19504 −
AIN1−OUT a C0400 − − − − −
Special features of AIN1
l A dead band element can be integrated into the output signal at AIN1 via code C0034.
Together with the jumper position X2 (controller front) the function 4 ... 20 mA can be
implemented as a master current value.
l The signal is read cyclically (1 ms).
3
4
AIN2
+
+
AIN2-OUT
AIN2-GAIN
AIN2-OFFSET
C0409/1
C0409/2
C0407
C0408
C0405
Fig. 3−48 Analog input via terminal X6/3, X6/4 (AIN2)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
AIN2−OFFSET a C0409/1 dec [%] C0407 1 19503 −
AIN2−GAIN a C0409/2 dec [%] C0408 1 19505 −
AIN2−OUT a C0405 − − − − −
Special feature of AIN2
l The signal is read cyclically every 250 ms.