Function library
Function blocks
3.5.57 Sample and hold function (S&H)
3−248
l
EDSVS9332P−EXT DE 2.0
3.5.57 Sample and hold function (S&H)
Purpose
The FB can save analog signals. The saved value is also available after mains switching.
C0572
S&H1
S&H1-OUT
S&H1-IN
C0573
S&H1-LOAD
C0570
C0571
S&H
Fig. 3−196 Sample and hold function (S&H1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
S&H1−IN a C0572 dec [%] C0570 1 1000
S&H1−LOAD d C0573 bin C0571 2 1000 LOW = save
S&H1−OUT a
Function
l With S&H1−LOAD = HIGH the signal at the input S&H1−IN is switched to the output
S&H1−OUT.
l With S&H1−LOAD = LOW the output S&H1−OUT is disconnected from the input S&H1−IN and
outputs the value which was last valid.
Saving in the case of mains disconnection:
l Keep S&H1−LOAD at LOW level when disconnecting the supply voltage (mains, DC bus or
terminal 59).
l Keep S&H1−LOAD at LOW level when connecting the supply voltage (mains, DC bus or
terminal 59).