Function library
Function blocks
3.5.32 Freely assignable digital inputs (DIGIN)
3−185
l
EDSVS9332P−EXT DE 2.0
3.5.32 Freely assignable digital inputs (DIGIN)
Purpose
Reading and conditioning of the signals at the terminals X5/E1 to X5/E5.
E1
E2
E3
E4
E5
1
0
C0114/1...5
DIGIN
DIGIN1
DIGIN2
DIGIN3
DIGIN4
DIGIN5
C0443
28
DCTRL -X5/28
X5
DIGIN-CINH
1
Fig. 3−135 Freely assignable digital inputs (DIGIN)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DIGIN−CINH d dec Controller inhibit acts directly on the DCTRL
control
DIGIN1 d C0443 dec
DIGIN2 d C0443 dec
DIGIN3 d C0443 dec
DIGIN4 d C0443 dec
DIGIN5 d C0443 dec
Function
The terminals X5/E1 to X5/E5 are scanned every millisecond. The level for every input can be
inverted. For this, proceed as follows:
l Select code C0114 with corresponding subcode (e.g. subcode 3 for input X5/E3)
l Enter the desired level as a parameter:
0 = Level not inverted (HIGH active)
1 = Level inverted (LOW active)