Residual hazards
Even if notes given are taken into c
onsideraon and protecve measures are implemented,
the occurrence of residual risks cannot be fully prevented.
The user must take the residual hazards menoned into consideraon in the risk assessment
for his/her machine/system.
If the above is disregarded, this can lead to severe injuries to persons and damage to
property!
Product
Observe the warning labels on the product!
Dangerous electrical voltage:
Be
fore working on the product, make sure there is no voltage applied to the power terminals!
Aer mains disconnecon, the power terminals will sll carry the hazardous electrical voltage
for the me given next to the symbol!
Electrostac sensiv
e devices:
Before working on the product, the sta must ensure to be free of electrostac charge!
High leakage current:
Carr
y out xed installaon and PE connecon in compliance with:
EN 61800‑5‑1 / EN 60204‑1
Hot surface:
Use per
sonal protecve equipment or wait unl the device has cooled down!
Degree of pr
otecon - protecon of persons and device protecon
•
In
formaon applies to the mounted and ready-for-use state.
•
Informaon does not apply to the wire range of the terminals.
-
Terminals that are not wired have low protecon against physical contact.
-
Terminals for large cable cross-secons have lower classes of protecon, e. g. from
15 kW IP10 only.
Protecon of per
sons
Before working on the inverter, check if no voltage is applied to the power terminals.
•
Depending on the device, the power terminals X105 remain live for up to 20 minutes.
•
The power terminals X100 and X105 remain live even when the motor is stopped.
Device protecon
•
The ma
ximum test voltage for insulaon tests between a control potenal of 24 V and PE
must not exceed 110 V DC (EN 61800‑5‑1).
Motor pr
otecon
With some sengs of the inverter, the connected motor can be overheated.
•
E. g. by longer operaon of self-venlated motors at low speed.
•
E. g. by longer operaon of DC-injecon braking.
Protecon of the machine/system
Drives can reach dangerous overspeeds.
•
E. g. by seng high output frequencies in connecon with motors and machines not
suitable for this purpose.
•
The inverters do not provide protecon against such operang condions. For this
purpose, use addional components.
Switch contactors in the motor cable only if the controller is inhibited.
•
Switching while the inverter is enabled is only permissible if no monitoring funcons are
acvated.
Safety ins
trucons
Residual hazards
30