Fusing data
A residual current device (RCD) is oponal.
Fusing da
ta for UL/NEC compliant installaons: 4Fusing data ^ 56
Supplier Fuse Circuit breaker RCD
Max.
SCCR
Characterisc
Max. rated
curr
ent
Max.
SCCR
Characterisc
Max. rated
current
Type
kA A kA A mA
i700-CV30/400-3 gG/gL, gRL 40 C 40 ≥ 300 Typ B
i700-CV60/400-3 gG/gL, gRL 63 C 63 ≥ 300 Typ B
Connecon da
ta
i700-CV30/400-3 ... i700-CV60/400-3
Connecon descripon Mains c
onnecon
Connecon X100
Terminal type Schraubklemme
Max. Cable cross-secon mm² 16
Max. Cable cross-secon AWG 6
Min. Cable cross-secon mm² 0.5
Min. Cable cross-secon AWG 20
Stripping length mm 12
Stripping length in 0.5
Tightening torque Nm 1.5
Tightening torque lb-in 13.3
Required tool Screwdriver 1.0 x 5.5
i700-CV30/400-3 ... i700-CV60/400-3
Connecon descripon DC connecon
Connecon X101
Terminal type Schienensystem
Tightening torque Nm 5
Tightening torque lb-in 44.3
Required tool Crossp screwdriver PH3
i700-CV30/400-3 ... i700-CV60/400-3
Connecon descripon PE connecon
Connecon Symbol Schutzerde (PE)
Terminal type Schienensystem
Tightening torque Nm 2.5
Tightening torque lb-in 22.1
Required tool Crossp screwdriver PH2
Technical data
3-phase mains c
onnecon 480 V
Power supply data
88