Inverter Operang condions Line reactor - Lenze type designaon
I95AE315F
400 V
480 V
EZAELN3040
EZAELN3035
EZAELN3025
EZAELN3020
E84AZESR1834 I0FAE315F
I95AE322F
400 V
-
EZAELN3063
EZAELN3050
EZAELN3045
EZAELN3040
EZAELN3035
E84AZESM2234 I0FAE322F
I95AE330F
400 V
-
EZAELN3080
EZAELN3063
EZAELN3050
EZAELN3045
EZAELN3040
E84AZESM3034 I0FAE330F
I95AE345F
400 V
480 V
EZAELN3100
EZAELN3090
EZAELN3080
EZAELN3063
EZAELN3050
E84AZESM4534 I0FAE345F
I95AE355F
400 V
480 V
EZAELN3125
EZAELN3100
EZAELN3090
EZAELN3080
EZAELN3063
- I0FAE355F
I95AE375F
400 V
480 V
EZAELN3160
EZAELN3125
EZAELN3100
EZAELN3090
- I0FAE375F
I95AE390F
400 V
480 V
EZAELN3180
EZAELN3160
- IOFAE411F
I95AE411F
400 V
480 V
EZAELN3200
EZAELN3180
- IOFAE411F
WARNING!
▶
UL marking
▶
The integral solid state short circuit pr
otecon included in the inverter does not provide branch circuit
protecon. Branch circuit protecon must be provided in accordance with the Naonal Electrical Code /
Canadian Electrical Code and any addional local codes.
▶
Marquage UL
▶
La protecon staque intégrée contre les courts-circuits n’ore pas la même protecon que le disposif
de protecon du circuit de dérivaon. Un tel disposif doit être fourni, conformément au Naonal
Electrical Code / Canadian Electrical Code et aux autres disposions applicables au niveau local.
WARNING!
▶
UL marking
▶
Use 75 °C copper wire only, except for control circuits.
▶
Marquage UL
▶
Uliser e
xclusivement des conducteurs en cuivre 75 °C, sauf pour la pare commande.
Electrical ins
tallaon
Connecon according to UL