Absicherungsdaten
Branch Circuit Protecon (BCP)
Short Circuit Current Rangs (SCCR) with Standard Fuses and Circuit Breaker
(Tested per UL61800-5-1, reference UL le E132659)
These devices are suitable for motor group installaon when used with Standard Fuses and Circuit Breaker.
For single motor installaon, if the fuse value indicated is higher than 400 % of the motor current (FLA), the
fuse value has to be calculated. If the value of the fuse is below two standard rangs, the nearest standard
rangs less than the calculated value shall apply.
Umrichter Standard Fuses (UL248) Circuit Breaker (UL489)
Mains
Rated
power
SCCR Max. rated current Class SCCR Max. rated current Min. cabinet dimensions
kW HP kA A kA A m³ ³
230 V, 1/3-ph 0.37 0.5 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 0.55 0.75 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 0.75 1 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 1.5 2 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 3-ph 2.2 3 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 3-ph 4 5 65 60 CC, CF, J, T 65 60 0.042 1.48
230 V, 3-ph 5.5 7.5 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 0.55 0.75 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 0.75 1 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 2.2 3 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 4 5 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 7.5 10 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 11 15 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 15 20 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 22 30 65 70 CC, CF, J, T 65 70 0.17 6
480 V, 3-ph 30 40 22 125 CC, CF, J, T 35 125 0.57 20
480 V, 3-ph 45 60 22 125 CC, CF, J, T 35 125 0.57 20
480 V, 3-ph 55 75 22 200 CC, CF, J, T 35 200 0.57 20
480 V, 3-ph 75 100 22 200 CC, CF, J, T 35 200 0.57 20
480 V, 3-ph 90 125 22 300 CC, CF, J, T 10 300 0.57 20
480 V, 3-ph 110 150 22 300 CC, CF, J, T 10 300 0.57 20
Elektrische Ins
tallaon
Anschluss nach UL
Absicherungsdaten
42