Terminal data
Rated power P
rated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Mains c
onnecon
Connecon X100
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5 16
Max. cable cr
oss-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool 0.5 x 3.0 0.8 x 4.0
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon PE c
onnecon
Connecon PE
Max. cable cr
oss-secon mm² 6 16
Max. cable cr
oss-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.4
Tightening torque Nm 2 3.4
Tightening torque lb-in 18 30
Required tool T20 PZ2
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Motor c
onnecon
Connecon X105
Connecon type Pluggable
Max. cable cr
oss-secon mm² 2.5 16
Max. cable cr
oss-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool 0.5 x 3.0 0.8 x 4.0
Fusing data
A residual current device (RCD) is oponal.
Inverters Fuse Circuit breaker RCD
Characterisc
Max. rated
curr
ent
Characterisc
Max. rated
current
Type
A A mA
I95AE137D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE155D gG/gL, gRL 10 B 10 ≥30 Typ B
I95AE175D gG/gL, gRL 16 B 10 ≥30 Typ B
I95AE215D gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE222C gG/gL, gRL 16 B 16 ≥30 Typ B
I95AE240C gG/gL, gRL 50 B 50 ≥300 Typ B
I95AE255C gG/gL, gRL 50 B 50 ≥300 Typ B
Electrical ins
tallaon
Mains connecon
3-phase mains connecon 230/240 V
141