- 142 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Specification
1. Specification
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV : Electronic Expansion Valve
5. To be added for more available Models
Type
Model Unit
W
Cooling Capacity kcal/h
Btu/h
W
Heating Capacity kcal/h
Btu/h
Dimensions (W*D*H)
Body
mm
inch
Coil
Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number
W
Running Current A
Fan Air Flow Rate(H/M/L) cmm
cfm
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side mm(inch)
Pipe Connections
Gas Side mm(inch)
Drain Pipe(Internal Dia.)
mm
Net Weight kg(lbs)
Noise Level
(Sound Press, 1.5m, H/M/L)
dBA±3
Power Supply Ø / V / Hz
Refrigerant Control
Power cable mm
2
Transmission cable mm
2
Color
Ceiling & Floor
ARNU09GVEA1 ARNU12GVEA1
2,800 3,600
2,400 3,100
9,600 12,300
3,200 4,000
2,800 3,400
10,900 13,600
900x200x490 900x200x490
35.4x7.9x19.3 35.4x7.9x19.3
2x12x20 2x12x20
0.10 0.10
Cross Flow Fan Cross Flow Fan
30 30
0.13 0.13
7.6/6.9/6.2 9.2/7.6/6.9
268/244/219 325/269/244
Direct Direct
BLDC BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene
Fuse Fuse
Ø6.35(1/4) Ø6.35(1/4)
Ø12.7(1/2) Ø12.7(1/2)
16 16
12(26.5) 12(26.5)
36/32/28 38/36/30
1, 220 ~ 240, 50 1, 220 ~ 240, 50
1, 220, 60 1, 220, 60
EEV EEV
CV2.0 X 3C CV2.0 X 3C
CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C
Morning fog Morning fog