- 201 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
2.1.2 Oil return control on heating mode
■ Oil return operation time : 3 min for running step
■ Min. frequency
• temp. out > -5˚C: 30Hz temp. out -5˚C: 40Hz
■ Starting condition:same as cooling mode