EasyManua.ls Logo

Mircom FA-200 Series - Module Settings; Main Fire Alarm Module; Figure 5: Main Fire Alarm Module

Mircom FA-200 Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FA-200 Series Installation and Operation Manual
9
Module Settings
Main Fire Alarm Module
Class A / B Selection
On the FA-202, FA-204 and FA-204E only, JW1 & JW2 are connected from 1 to 2 for initiating circuit Class B (Style
B) operation, and from 2 to 3 for Class A (Style D) operation. These are not present on the FA-201, and only JW2 is
present on the FA-202.
Zone Adder Module: On an FA-204E only, remove the jumper on JW4 if a DM-204 Zone Adder Module is installed.
The zone adder module is plugged into P6 & P7.
Relay Module: Remove the jumper on JW3 if an RM-204 or RM-208 Relay Module is installed. The relay module is
plugged into P1.
Digital Communicator: Remove the jumper on JW6 if a DACT-100A Digital Communicator is installed. The digital
communicator is plugged into P8.
City Tie: Remove the jumper on JW6 if a PR-100 City Tie is installed. The City Tie is plugged into P8.
Battery: Connected to P2(+) & P3(-) via the factory installed cables.
Transformer: Factory wired to P4 & P5, do not disconnect.
JW5: There should be no jumper here; do not use.
SW9,11,13: Configuration DIP switches.
Battery Fuse F1: Replace with 10 amp, 1-1/4" fast acting fuse.
Figure 5: Main Fire Alarm Module
Note: The Class A/B selection affects all initiating circuits, and must be used with the correct Configuration
DIP switch setting.
P6
F1
10 AMP
BATTERY
FUSE
SW13
1
2
3
JW2
P3
231
BATT+
P4
P5
P2
BATT-
XMFR
XMFR
JW1
P7
P8
JW4
JW5
JW3
JW6
SW11
SW9
P1
SUPV RLY
COM-
COM+
S
IND2-
IND2-
IND1-
IND1-
IND1+
IND1+
INI4-
INI4+
INI3-
INI3+
INI2-
INI2+
INI1-
INI1+
485-
485+
-
+
TRB
TRL
IND2+
IND2+
NO
NC
COM
ALM RLY
NO
NC
COM
TBL RLY
4 WIRE
NO
NC
COM
Note: Do not plug DACT into P1 on main
board. Plug into P8 only when system is
powered off.
Note: Do not plug RM-204/
208 into P8 on main board.
Plug into P1 only when
system is powered off.

Table of Contents

Related product manuals