FA-200 Series Installation and Operation Manual
39
FA-204 Fire Alarm Control Panel
Same as FA-201, plus ...
Four supervised Class B (Style B) or two Class A ( Style D) Initiating circuits; configurable (normal or verified,
and for Class B there may be one waterflow and one supervisory). [Compatibility ID “A”]
Optional RM-204 or RM-208 Relay Module.
One RS-485 connection for up to 3 RAM-208 Remote Annunciators.
Auxiliary relays: (resistive loads) common alarm, supervisory, trouble
all are Form C, 1 amp, 28VDC
DACT / Dialler Module (DACT-100A)
DACT - “Digital Alarm Communicator Transmitter”
Using Ademco Contact ID and SIA-DCS Protocols.
See Mircom document LT-617 for further info.
Current Consumption: standby: 45 mA
alarm: 120 mA
Polarity Reversal and City Tie Module (PR-100)
Supervised city tie: not power limited
24VDC unfiltered, 210 mA max., Trip coil: 14 ohms
Polarity reversal: power limited
24VDC open, 12VDC @ 3.5 mA, 8 mA max. (shorted)
Current consumption: standby: 35 mA
alarm: 300 mA
RM-204 / RM-208 Relay Module
Four or eight relays: Form C, 1A (resistive), 28 VDC per contacts
Each individual relay can be relay per zone, common alarm, common supervisory
Current Consumption: standby: 5 mA
alarm: 160 mA
FA-204E Fire Alarm Control Panel
General
Four supervised Style B (Class B) or 2 Style D (Class A) initiating circuits; configurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
Two Class A/B (Style Y/ Z) indicating circuits; configurable as strobes or audibles.
Power limited:24 VDC unfiltered
1.7 A @ 49°C per circuit (5A total)
One DM-204 Zone Adder Module may be added.
Initiating circuit disconnect switches.
Optional DACT or city tie adder module.
Optional RM-204 / RM-208 Relay Module.
Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
Aux power supply.
Power limited: 24VDC, 300mA max, unfiltered
for RTI or Remote Annunciators
1 RS-485 connection for up to 3 RAM-208 Remote Annunciators.
1 RTI interface for connection to an RTI Remote Trouble Indicator.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-200 Series and is the answer not in the manual?

Mircom FA-200 Series Specifications

General IconGeneral
BrandMircom
ModelFA-200 Series
CategoryControl Panel
LanguageEnglish

Related product manuals