FA-200 Series Installation and Operation Manual
1
Introduction
About this Manual
This installation and operation manual provides information on installing and operating the FA-200 Microprocessor-
Based Fire Alarm Control Panel.
About the FA-200
Mircom's FA-200 Fire Alarm Control Panels provide 1, 2, 4, or 8 supervised Class B (ULI Style B) Initiating Circuits,
or 1, 2, 4 supervised Class A (ULI Style D) Initiating Circuits, and 2 or 4 supervised Class A or B (ULI Style Z or Y)
Indicating Circuits. All Circuits are supervised for opens and ground faults, and Indicating Circuits for shorts.
Optional Modules include a DM-204 Zone Adder (required for full capacity in the FA-204E only), a DACT-100A
Dialler or a PR-100 Polarity Reversal & City Tie Module, and RM-204 or RM-208 Relay Modules. The two
enclosures are flush or surface mountable, and can be used for retrofits and on new installations.
Overall Features:
The small enclosure versions, FA-201, FA-202, & FA-204, have 1, 2, 4 Class B (Style B) initiating circuits
respectively. The FA-202 & FA-204 may be configured as 1 or 2 Class A (Style D) Circuits respectively. These
also have 2 Power Limited Class A/B (Style Z/Y) indicating circuits with individual trouble indicators.
The large enclosure version, FA-204E, has four Class B (Style B) initiating circuits which may be configured as
two Class A (Style D) circuits respectively. It also has two power limited Class A/B (Style Z/Y) indicating circuits
with individual trouble indicators. With a DM-204 Zone Adder Module, an extra four Class B (2 Class A)
initiating circuits, and two Class A/B indicating circuits are added.
Each initiating circuit is configurable as a normal or verified alarm. In addition, on a Class B FA-204 or fa-204e,
Initiating Circuit three may be a Waterflow Zone (as may Initiating Circuit 7 if a DM-204 is installed), and
initiating circuit four may be a latched or non-latched supervisory zone (as may initiating circuit eight if a DM-
204 is installed). On a Class A FA-204E with a DM-204, initiating circuit three may be a waterflow zone and
initiating circuit four may be a latched or non-latched supervisory zone.
Indicating circuits can be configured as audible or visual and as silenceable or non-silenceable. Audibles may
be steady, temporal code, california code, or march time.
Initiating circuits may be individually disconnected by a slide-switch.
Configurable signal silence inhibit (disabled or 1 minute), auto signal silence (disabled or 5, 10, 20 minutes),
and one-man walk test.
Subsequent alarm, supervisory, and trouble operation.
Four-wire resettable smoke power supply (200 mA max.).
Auxiliary relay contacts for common alarm and common supervisory (disconnectable), and a common trouble
relay. If no Supervisory zones are configured then the common supervisory relay can be used as an extra
common alarm relay.
Interface for an RTI Remote Trouble Indicator.
RS-485 Interface for 1 to 3 of RAM-208 Remote Multiplex Annunciators on FA-204 & FA-204E.
The FA-201, FA-202, FA-204 may use one of optional DACT-100A (Dialler), PR-100 (City Tie), RM-204 or RM-
208 Relay Modules.
The FA-204E may use one of optional DACT-100A (Dialler), PR-100 (City Tie), and one of
RM-204 or RM-208 Relay Modules.
Slide Switch controls and LED Common indicators.
Easy configuration via DIP switches.
Extensive transient protection.
Technical Support
For all technical support inquiries, please contact Mircom’s Technical Support Department between 8 A.M. and 5
P.M. (EDT) Monday through Friday, excluding holidays.
Local Phone: 905-695-3535 Toll-Free Phone: 1-888-449-3535
Local Fax: 905-660-4113 Toll-Free Fax: 1-888-660-4113

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-200 Series and is the answer not in the manual?

Mircom FA-200 Series Specifications

General IconGeneral
BrandMircom
ModelFA-200 Series
CategoryControl Panel
LanguageEnglish

Related product manuals