System Configuration
30
When configuring the FA-200 main board, keep in mind the following information:
Only indicating circuit two may be configured for visual devices.
If initiating circuit three is configured as waterflow, the corresponding verified selection becomes a retard
selection.
If initiating circuit four is configured as alarm, the corresponding latching selection has no effect.
If initiating circuit four is configured as supervisory, the corresponding verified selection has no effect.
The selection of Class A/B (Style Z/Y) indicating circuits is only a matter of how they are wired. See connection
information on page 13 .
If Class A (Style D) initiating circuits are selected (FA-202, FA-204, FA-204E only), the appropriate board
jumpers must also be set. Class B initiating circuits one and two combine to create Class A Circuit #1, and Class
B initiating circuits three and four combine to create Class A Circuit #2. DIP switches for circuits three and four
are ignored except for an FA-204E with a DM-204 Adder Module. LED indicators for circuits three and four are
non-functional except for an FA-204E with a DM-204 Adder Module.
DM-204 Module
On the DM-204 Zone Adder Module the DIP switches are located on the bottom right-hand corner.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-200 Series and is the answer not in the manual?

Mircom FA-200 Series Specifications

General IconGeneral
BrandMircom
ModelFA-200 Series
CategoryControl Panel
LanguageEnglish

Related product manuals