EasyManuals Logo
Home>Nice>Control Unit>MC424L

Nice MC424L User Manual

Nice MC424L
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
ENGLISH – 13
LEVEL 1 FUNCTIONS (ON-OFF)
LED Function Description
L5
Electric lock /
OGI (Open Gate
Indicator)
Function ENABLED: OGI (Open Gate Indicator).
If the function is enabled, terminals 3-4 can be used to connect an open gate indicator light (24 V).
Function NOT ENABLED: electric lock.
If the function is not enabled, terminals 3-4 can be used to connect the electric lock.
L6 Pre-ashing
Function ENABLED: the warning light starts ashing 3 seconds before the start of the manoeuvre to
signal in advance a dangerous situation.
Function NOT ENABLED: the warning light starts ashing when the manoeuvre starts.
L7
Condominium
function
Function ENABLED: each command received triggers an opening manoeuvre that cannot be interrupted
by subsequent command impulses.
Function NOT ENABLED: each command received triggers an OPEN-STOP-CLOSE-STOP sequence,
which is useful when many people use the automation with radio commands.
L8 Light/Heavy Gates
Function ENABLED: if the function is enabled, the control unit can be congured to control heavy gates
by setting the acceleration ramp and closing slowdown speeds differently.
Function NOT ENABLED: if the function has not been enabled, the control unit is set for controlling light
gates.
6.4 LEVEL 2 PROGRAMMING (ADJUSTABLE PARAMETERS)
All Level 2 parameters are set by default as shown under “GREYin “Table 8and can be modied at any time. The parameters
can be adjusted to a value between 1 and 8. To check the value corresponding to each LED, refer to “Table 8”.
6.4.1 Level 2 programming procedure
m
The user has maximum 10 seconds to press the buttons consecutively during the programming procedure,
after which time the procedure terminates automatically and memorises the changes made up to then.
To perform Level 2 programming:
1. press and hold the [Stop/Set] button until LED “L1” starts ashing
2. press the [Open
p
] or [Close
q
] button to move the ashing LED to the “entry LED” associated with the parameter to be
modied
3. press and hold the [Stop/Set] button. With the [Stop/Set] button pressed:
wait roughly 3 seconds, until the LED representing the current level of the parameter to be modied lights up
press the [Open
p
] or [Close
q
] button to shift the LED associated with the parameter’s value
4. release the [Stop/Set] button
5. wait 10 seconds (maximum time) to exit the programming mode.
l
To set multiple parameters during the procedure's execution, repeat the operations from point 2 to point 4 dur-
ing the phase itself.
l
The set value highlighted in grey (“Table 8”) indicates that is the default value.
Table 8
LEVEL 2 FUNCTIONS (ADJUSTABLE PARAMETERS)
Entry
LED
Parameter
LED
(level)
Set value Description
L1 Pause Time
L1 5 seconds
Adjusts the pause time, in other words, the time that elapses before
automatic re-closure. It is only effective if the Close function is
enabled.
L2 15 seconds
L3 30 seconds
L4 45 seconds
L5 60 seconds
L6 80 seconds
L7 120 seconds
L8 180 seconds

Table of Contents

Other manuals for Nice MC424L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nice MC424L and is the answer not in the manual?

Nice MC424L Specifications

General IconGeneral
BrandNice
ModelMC424L
CategoryControl Unit
LanguageEnglish

Related product manuals