6 Programless Communications
6 - 44
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
(2) We will change the communications settings for CH1.
Change the following settings, and then click the OK Button. Use the defaults settings for
the other parameters.
Parity Bit: Exist
Even/odd parity: Even
Stop bit: 2
Sum check code: Exist
Online Change: Enable
Setting modifications: Enable
Communication rate setting: 57600 bps (This setting can be changed after you change
the communication protocol setting.)
Communication protocol setting: MC protocol (Format 4)
Note: If you change the station number setting, refer to 6-2-7 Communications Node Number
(3) Select Online - Write to PLC. A dialog box to write the set values will be displayed.