6 Programless Communications
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
6-6 Connecting to MELSEC Q-series PLCs
6
6-6-5 Checking Operation
(2) We will initialize the download areas with the set values from the E5CC-T Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CC-T Controllers.
Double-click D25 (Request Flag) on the Device Memory Dialog Box. The following dialog
box is displayed. Enter 2 (Initialize Download Areas), click the Set Button, and then click the
Close Button.
(3) We will confirm that the download areas have been initialized.
When initialization is completed, D0 (Response Flag) will change to 1 (Normal End) and
D25 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
area to see if it has been initialized to the values given in the above table.
Confirm this for the No. 1 and No. 2 Controllers as well.