74
Startup Compensation Time
The interval between the moment the K3NR is turned and the moment the
K3NR starts measurement operation is set in the option menu.
The startup compensation time parameter keeps the measurement operation
from sending an unnecessary output corresponding to instantaneous, fluctu-
ating input from the moment the K3NR is turned ON until the end of the preset
period.
Setting range Unit Default
0.0 to 99.9
S 0.0
The K3NR will display “00000” with all outputs turned OFF until the K3NR is in
measurement operation.
L set value
L comparative output
Power ON
Display = 00000
(measurement
interrupted)
Setting time
Display
Time
Follow the steps described below to set the startup compensation time to 2 seconds.
Set Value LED Display Model Basic Model
1, 2, 3... 1. Press the Mode Key for more than one second while the opt option menu is
displayed. The aUg process time for averaging measured value setting will
appear.
Set Value LED Display Model Basic Model
stime
FUNCTION
SETTING
REFERENCE
SETTING
EXAMPLE
Setting Mode
Section 4-2